Abstract:
fault warning results caused by insensitive capture of weak features in distribution transformer winding loosening fault warning. Firstly,the force energy of the winding is introduced as a modulation parameter to reconstruct the mother wavelet function, breaking through the limitations of traditional fixed time-frequency analysis and achieving multi-scale accurate extraction of fault signals;Then,based on the signal decomposition results,the feature frequency amplitude changes and weight coefficients are fused to construct a quantitative fault index and a three-level warning mechanism,solving the problem of delayed response to progressive faults with a single threshold;Finally,experiments have shown that this method can reduce the distance detection error to 0.01mm and the partial discharge detection error to 0pC,verifying its high sensitivity and reliability in fault warning.